ET-7019Z_S2_DESCRIPTION.html
The ET-7019Z/S2 and is a testament to the excellence of ICP DAS products. The ET-7019Z/PET-7019Z/ET-7219Z/PET-7219Z is specifically designed for extremely accurate thermocouple measurement and features automatic coldjunction compensation for each channel to ensure temperature output consistency and stable temperature output in the field. Current input and voltage input are both supported. Another feature is that its ten input channels can be individually configured for different kinds of analog input. Open thermocouple detection and ESD/EFT/Surge protection mechanisms are also included. The six/five digital output channels can be set as alarm outputs with short-circuit protection and overload protection.
ET-7019Z_S2.html
System Specifications
Built-In Web Server
|
Yes
|
Web HMI
|
Yes
|
I/O Pair Connection
|
Yes
|
Ethernet Port
|
1 x RJ-45, 10/100 Base-TX
|
PoE
|
-
|
Protocol
|
Modbus/TCP, Modbus/UDP
|
Security
|
ID, Password and IP Filter
|
Dual Watchdog
|
Yes, Module (0.8 second), Communication (Programmable)
|
for System Running
|
Yes
|
for Ethernet Link/Act
|
Yes
|
for DI/DO status
|
-
|
for PoE Power
|
-
|
Ethernet
|
1500 VDC
|
I/O
|
2500 VDC
|
ESD (IEC 61000-4-2)
|
4 kV Contact for Each Terminal and 8 kV Air for Random Point
|
EFT (IEC 61000-4-4)
|
+/-4 kV for Power
|
LED Indicators
|
Yes,1 as Power, 1 as Alarm Indicator. 1 as Communication Indicator.
|
ESD (IEC 61000-4-2)
|
± 4 kV Contact for each Terminal, ± 8 kV Air for Random Point
|
EFT (IEC 61000-4-4)
|
± 4 kV for Power Line
|
Reverse Polarity Protection
|
Yes
|
Powered from Terminal Block
|
10 ~ 30 VDC
|
Powered from PoE
|
-
|
Consumption
|
2.6 W (Max.)
|
Dimensions (W x L x H)
|
72 mm x 123 mm x 35 mm
|
Installation
|
DIN-Rail or Wall mounting
|
Operating Temperature
|
-25 ~ +75C
|
Storage Temperature
|
-30 ~ +80C
|
Humidity
|
10 to 90% RH, Non-condensing
|
I/O Specifications
Channels
|
10 (Differential)
|
Sensor Type
|
+/-15 mV, +/-50 mV, +/-100 mV, +/-150 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, +/-10 V,
+/-20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable) Thermocouple (J, K, T, E, R, S, B, N, C, L,
M, and LDIN43710)
|
Individual Channel Configuration
|
Yes
|
Resolution
|
16-bit
|
Sampling Rate
|
10 Samples/Second (Total)
|
Accuracy
|
+/-0.1% of FSR or better
|
Zero Drift
|
+/-0.5 ±V/C
|
Span Drift
|
+/-25 ppm/C
|
Over Voltage Protection
|
240 Vrms
|
Input Impedance
|
>300 kΩ
|
Common Mode Rejection
|
86 dB Min.
|
Normal Mode Rejection
|
100 dB
|
Temperature Output Consistency
|
Yes
|
Stable Temperature Output in the Field
|
Yes
|
Open Wire Detection
|
Yes
|
Virtual Channel to Channel Isolation
|
+/-400 VDC
|
Channels
|
6
|
Type
|
Isolated Open Collector
|
Sink/Source (NPN/PNP)
|
Sink
|
Max. Load Current
|
700 mA/Channel
|
Load Voltage
|
5 VDC ~ 50 VDC
|
Overvoltage Protection
|
60 VDC
|
Overload Protection
|
1.4 A
|
Short-circuit Protection
|
Yes
|
Power-on Value
|
Yes, Programmable
|
Safe Value
|
Yes, Programmable
|
|