I-97015_DESCRIPTION.html
The I-97015 is an8-channel RTD input module designed to measure temperature using RTD. Each channel can be connected to a various kinds of RTD sensors. The module features automatic compensation for three-wire RTD.
I-97015.html
Interface
|
RS-485
|
Format
|
N, 8, 1
|
Baud Rate
|
1200 to 115200 bps
|
Protocol
|
DCON
|
Dual Watchdog
|
Yes, Module (1.6 Seconds), Communication (Programmable)
|
System LED Indictor
|
1 LED as Power Indicator
|
I/O LED Indicator
|
16 LEDs as Digital Input Indicators
|
Intra-module Isolation, Field-to-Logic
|
3000 VDC
|
ESD (IEC 61000-4-2)
|
±4 kV Contact for each Terminal ±8 kV Air for Random Point
|
RS Immunity (IEC 61000-4-3)
|
3 V/m, 80 MHz ~ 1 GHz
|
Power Consumption
|
0.6 W Max.
|
Dimensions (L x W x H)
|
144 mm x 30.3 mm x 134 mm
|
Operating Temperature
|
-25C ~ +75C
|
Storage Temperature
|
-40C ~ +85C
|
Humidity
|
10 ~ 90% RH, non-condensing
|
I/O Specifications
Channels
|
8 (Form A)
|
Wiring
|
2/3-Wire
|
Sensor Type
|
Pt100, Pt1000, Ni100, Ni120, Cu50, Cu100, Cu1000
|
Accuracy
|
16-bit
|
Resolution
|
±0.05% of FSR
|
-3dB Bandwidth
|
15.7 Hz
|
Sampling Rate
|
12 Hz (Total)
|
Zero Drift
|
±0.5 μV/C
|
Span Drift
|
±20 ppm/C
|
Common Mode Rejection
|
150 dB
|
Normal Mode Rejection
|
100 dB
|
Input Impedance
|
>1 MΩ
|
Individual Channel Configuration
|
Yes
|
3-wire RTD Lead Resistance Elimination
|
Yes
|
Resistance Measurement
|
3.2 kΩ
|
Open Wire Detection
|
Yes
|
Overvoltage Protection
|
±120 VDC
|
|