ICP DAS PET-7017-10 - ICP DAS 10/20-channel Voltage & Current Analog Input Module with High Voltage Protection PoE Module by ICP DAS
|
|
|
|
- PoE and Regular Ethernet Options
- Built-In Web Server
- Web HMI
- Modbus/TCP, Modbus/UDP Protocol
- Communication Security
- Dual Watchdog
- Operating Temperature: -25 ~ +75 °C
- I/O Pair Connection
- Built-In I/O
|
|
|
The PET-7017-10, a web-based Ethernet I/O module, features a built-in web server which allows configuration, I/O monitoring and I/O control by simply using a regular web browser. Remote control is as easy as surfing the Internet.
Besides, with the web HMI function, no more programming or HTML skills are required; creating dynamic and attractive web pages for I/O monitoring and I/O control would be fun to engineers ever after. The PET-7000 offers easy and safe access for users from anytime and anywhere! In addition, the PET-7000 also supports Modbus/TCP protocol that makes perfect integration to SCADA software.
Furthermore, PET-7000 features "PoE" that not only data but also power is carried through an Ethernet cable. This feature makes installation of PET-7000 a piece of cake. Imagine that no more unnecessary wires, only an Ethernet cable takes care of everything in the field.
The ET-7017-10 is a 16-bit, 10-channel differential or 20-channel single-ended analog inputs module that provides programmable input range on all analog channels (+/-150 mV, +/-500mV, +/-1 V, +/-5 V, +/-10 V, +/-20 mA, 0~20 mA and 4~20 mA). Each analog channel is allowed to configure an individual range and has 240 Vrms high overvoltage protection. Jumper selectable for voltage or current input. The sampling rate of PET-7017 is changeable; there are fast mode and normal mode for your consideration. PET-7017 also has qualification for 4 kV ESD protection as well as 3000 VDC intra-module isolation.
| Software |
| Built-In Web Server |
Yes |
| Web HMI |
Yes |
| I/O Pair Connection |
Yes |
| Communication |
| Ethernet Port |
10/100 Base-TX with Auto MDI/MDI-X |
| Protocol |
Modbus/TCP, Modbus/UDP |
| Security |
ID, Password and IP Filter |
| Dual Watchdog |
Yes, Module (0.8 second), Communication (Programmable) |
| LED Indicators |
| L1 (System Running) |
Yes |
| L2 (Ethernet Link/Act) |
Yes |
| L3 (Ethernet 10/100 M Speed) |
Yes |
| PoE Power |
Yes |
| 2 Way Isolaiton |
| Ethernet |
- |
| I/O |
2500 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) |
4 kV Contact for each terminal and 8 kV Air for random point |
| EFT (IEC 61000-4-4) |
+/-4 kV for Power |
| Power Requirements |
| Reverse Polarity Protection |
Yes |
| Powered from terminal block |
Yes, 12 ~ 48 VDC |
| Powered from PoE |
Yes, IEEE 802.3af, Class1 |
| Consumption |
3.8 W |
| Mechanical |
| Dimensions (W x L x D) |
72 mm x 123 mm x 35 mm |
| Installation |
DIN-Rail or Wall mounting |
| Environment |
| Operating Temperature |
-25 °C ~ +75 °C |
| Storage Temperature |
-30 °C ~ +80 °C |
| Humidity |
10 ~ 90% RH, non-condensing |
I/O Specifications
| Analog Input |
| Input Channels |
10 differential or 20 single-ended (Note1),
software selectable |
| Input Type |
+/-150 mV, +/-500 mV, +/-1V, +/-5V, +/-10V
+/-20 mA ,0 ~ 20 mA, 4 ~ 20 mA
(jumper selectable) |
| Individual Channel Configuration |
Yes |
| Resolution |
Normal Mode |
16-bit |
| Fast Mode |
12-bit |
| Sampling Rate |
Normal Mode |
10 Samples/Sec. (Total) |
| Fast Mode |
60 Samples/Sec. (Total) |
| Accuracy |
Normal Mode |
+/-0.1% |
| Fast Mode |
+/-0.5% or better |
| Zero Drift |
+/-20 μV/°C |
| Span Drift |
+/-25 ppm/°C |
| Overvoltage Protection |
Differential |
240 Vrms |
| Single-ended |
150 Vrms |
| Input Impedance |
Voltage |
2 MΩ (Differential), 1 MΩ (Single-ended) |
| Current |
125 Ω |
| Common Mode Rejection |
86 dB Min. |
| Normal Mode Rejection |
100 dB |
|
|
|
|