WISE-7517M-10 - 10/20-channels AI and 2-port Ethernet Switch by ICP DAS
|
|
|
WISE-7517M-10_SUMMARY.html
- Runs on browsers, no extra software tool is required.
- No more programming, Web pages provided for control logic editing.
- IF-THEN-ELSE logic rules execution ability.
- Built-in I/O (AI: 10/20 Channels)
- Support I/O Moniitoring/Control, Counter, Timer, Schedule, Email sending and CGI Command sending operations.
- Modbus TCP Protocol for SCADA System Integration.
- IEEE 802.3af-compliant Power over Ethernet (PoE).
- 2-port Ethernet Switch for Daisy-Chain Topology.
- MQTT Protocol for IT & IoT (Internet of Things) System Integration.
|
|
|
WISE-7517M-10_DESCRIPTION.html
The WISE-7517M-10 has a built-in two-port Ethernet switch to implement daisy-chain topology. The cabling is much easier and total costs of cable and switch are significantly reduced.
WISE-7517M-10.html
Channels
|
10 differential or 20 single-ended
|
Type
|
±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V ±20 mA ,0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable)
|
Resolution
|
16-bit
|
Sampling Rate
|
10 Samples/Second (Total)
|
Accuracy
|
±0.1 %
|
Zero Drift
|
±20 ±V/C
|
Span Drift
|
±25 ppm/C
|
Overvoltage Protection
|
Differential
|
240 Vrms
|
|
Single-ended
|
150 Vrms
|
Common Voltage Protection
|
±200 VDC
|
Overcurrent Protection
|
Yes, 50 mA at 110 VDC
|
Virtual Channel to Channel Isolation
|
Yes, 400 VDC
|
Open Wire Detection for 4 ~ 20 mA
|
Yes
|
Input Impedance
|
Voltage
|
2 MO (Differential), 1 MO (Single-ended)
|
|
Current
|
125O
|
Common Mode Rejection
|
86 dB Min.
|
Normal Mode Rejection
|
100 dB
|
Note1: Differential mode can be used for
voltage input and current input. Single-Ended mode can be used for voltage input
only.
|
Ethernet Port
|
2 x RJ-45, 10/100 Base-TX, Swtich Ports
|
PoE
|
Yes
|
Protocol
|
Modbus TCP, MQTT
|
for System Running
|
Yes
|
for Ethernet Link/Act
|
Yes
|
for I/O Channel Status
|
Yes
|
for PoE Power
|
Yes
|
ESD (IEC 61000-4-2)
|
±4 kV Contact for Each Terminal and ±8 kV Air for Random Point
|
EFT (IEC 61000-4-4)
|
±2 kV for Power Line
|
Surge (IEC 61000-4-5)
|
±2 kV for Power Line
|
Reverse Polarity Protection
|
Yes
|
Powered from Terminal Block
|
12 ~ 48 VDC
|
Powered from PoE
|
Yes, IEEE 802.3af, Class1
|
Consumption
|
3.7 W (Max.)
|
Dimensions (L x W x H)
|
120mm x 97mm x 42mm
|
Installation
|
Wall mounting
|
Operating Temperature
|
-25 C ~ +75 C
|
Storage Temperature
|
-30 C ~ +80 C
|
Humidity
|
10 ~ 90% RH, non-condensing
|
Software Specifications
Rule Configuration Website
|
Access Web server on WISE controllers to edit and upload logic rules through web browser.
|
72 IF-THEN-ELSE Logic Rules
|
3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions
|
48 Internal Registers
|
Hold temporary variables and read/write data.
|
24 Timers
|
Delay / Timing functions.
|
24 Schedules
|
Setup prescheduled routine tasks.
|
24 Emails
|
Send Email messages to pre-set Email receivers.
|
24 CGI Commands
|
Send pre-set CGI commands.
|
24 Recipes
|
Set up THEN/ELSE action groups.
|
8 P2P remote modules
|
Set up the connection information for the remote WISE modules.
|
Modbus/TCP Protocol
|
Real time control and monitoring I/O channels and system status of controllers via SCADA software.
|
MQTT Protocol
|
Real time message publish/subscribe mechanism for I/O channels and system status via IT/IoT software.
|
AI Channel
|
=, >, <, =, = (value)
|
Internal Register
|
=, >, <, =, = (value)
|
Timer
|
Timeout, Not Timeout
|
Schedule
|
In Range, Out of Range
|
P2P
|
DI, AI, DI counter, DO counter, IR
|
Rule Status
|
Enable, Disable
|
Internal Register
|
Change the value
|
Timer
|
Start, Reset
|
Schedule
|
Enable, Disable
|
Email
|
Send
|
MQTT message
|
Send
|
CGI Commands
|
Send
|
Recipe
|
Execute
|
P2P
|
DO(On/Off), AO, IR
|
Rule Status
|
Enable, Disable
|
|