PET-7204 - PoE Ethernet I/O Module with 2-port Ethernet Switch, with 4-channels AI, 4-channels AO, 4-channels DI (RoHS) by ICP DAS
|
|
|
PET-7204_SUMMARY.html
- Built-in Web Server
- Web HMI
- Support for both Modbus TCP and Modbus UDP Protocols
- Communication Security
- 2-port Ethernet Switch for Daisy-Chain Topology
- Dual Watchdog
- Wide Operating Temperature Range: -25 ~ +75C
- I/O Pair Connection
- Built-in I/O
- AI: 4 Channels with 240 Vrms Overvoltage Protection
- AO: 4 Channels
- DI/Counter: 4 Channels
|
|
|
PET-7204_DESCRIPTION.html
The PET-7204 is a multi-function, 4-channel analog inputs, 4-channel analog outputs, 4-channel digital inputs module. The PET-7204 is equipped with various programmable analog inputs (+/-500 mV, +/-1 V, +/-5 V, +/-10 V, +/-20 mA, 0 ~ 20 mA and 4 ~ 20 mA), and analog outputs (+/-5 V, +/-10 V, 0 ~ 20 mA and 4 ~ 20 mA). Each analog input can configure a proper range with 240 Vrms high voltage protection. Each analog input/output can be programmed to accept current or voltage as input/output depending upon the position of corresponding jumper.
PET-7204.html
Built-In Web Server
|
Yes
|
Web HMI
|
Yes
|
I/O Pair Connection
|
Yes
|
Ethernet Port
|
2 x RJ-45, 10/100 Base-TX, Swtich Ports
|
PoE
|
Yes
|
Protocol
|
Modbus TCP, Modbus UDP
|
Security
|
ID, Password and IP Filter
|
Dual Watchdog
|
Yes, Module (0.8 seconds), Communication (Programmable)
|
for System Running
|
Yes
|
for Ethernet Link/Act
|
Yes
|
for DI/DO status
|
Yes
|
for PoE Power
|
Yes
|
ESD (IEC 61000-4-2)
|
+/-4 kV Contact for Each Terminal and �8 kV Air for Random Point
|
EFT (IEC 61000-4-4)
|
+/-2 kV for Power Line
|
Surge (IEC 61000-4-5)
|
+/-2 kV for Power Line
|
Reverse Polarity Protection
|
Yes
|
Powered from Terminal Block
|
12 ~ 48 VDC
|
Powered from PoE
|
Yes, IEEE 802.3af, Class1
|
Consumption
|
5.5 W (Max.)
|
Dimensions (W x L x H)
|
120 mm x 76 mm x 38 mm
|
Installation
|
DIN-Rail or Wall mounting
|
Operating Temperature
|
-25 ~ +75 C
|
Storage Temperature
|
-30~ +80 C
|
Humidity
|
10 ~ 90% RH, non-condensing
|
I/O Specifications
Channels
|
4 (Differential)
|
Type
|
+/-500 mV, +/-1 V, +/-5 V, +/-10 V +0 mA ~ +20 mA, +/-20 mA, 4 ~ 20 mA (Jumper Selectable)
|
Individual Channel Configuration
|
Yes
|
Resolution
|
16-bit
|
Sampling Rate
|
Normal Mode
|
10 Samples/Second (Total)
|
|
Fast Mode
|
50 Samples/Second (Total)
|
Accuracy
|
Normal Mode
|
+/-0.1%
|
|
Fast Mode
|
+/-0.5% or better
|
Zero Drift
|
+/-20 ?V/C
|
Span Drift
|
+/-25 ppm/C
|
Overvoltage Protectionp>
|
240 Vrms
|
Overcurrent Protection
|
50 mA max. at 110 VDC/VAC max.
|
Common Voltage Protection
|
+/-200 VDC
|
Overcurrent Protection
|
50 mA max. at 110 VDC/VAC max.
|
Overcurrent Protection
|
Yes, 50 mA at 110 VDC
|
Virtual Channel to Channel Isolation
|
Yes, 400 VDC
|
Open Wire Detection for 4 ~ 20 mA
|
Yes
|
Input Impedance
|
Voltage
|
2 M?
|
|
Current
|
125 ?
|
Common Mode Rejection
|
86 dB Min.
|
Normal Mode Rejection
|
100 dB
|
Channels
|
4
|
Type
|
+0 VDC ~ +5 VDC, +/-5 VDC, +0 VDC ~ +10 VDC, +/-10 VDC,+0 mA ~ +20 mA, +4 mA ~ +20 mA(Jumper
Selectable)
|
Individual Channel Confi guration
|
Yes
|
Resolution
|
12-bit
|
Accuracy
|
+/-0.1% of FSR
|
Voltage Output Capability
|
20 mA @ 10 V
|
Open Wire Detection
|
400 ?
|
Open Wire Detection
|
Yes, for 4 ~ 20 mA only
|
Power-on Value
|
Yes, Programmable
|
Safe Value
|
Yes, Programmable
|
Dry Contact (Source)
|
On Voltage Level
|
Close to GND
|
|
Off Voltage Level
|
Open
|
|
Effective Distance for Dry Contact
|
500 M Max.
|
Wet contact (Sink)
|
On Voltage Level
|
+1 VDC Max.
|
|
Off Voltage Level
|
+3.5 VDC ~ +30 VDC
|
Counters
|
Max. Count
|
4,294,967,285 (32 bits)
|
|
Max. Input Frequency
|
100 Hz
|
|
Min. Pulse Width
|
5 ms
|
Overvoltage Protection
|
30 VDC
|
|
|
|
l');
?>
|