| Ambient Conditions |
| Ambient temperature (operation) |
-40 °C ... 85 °C |
| Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
| Degree of protection |
IP20 |
| Protective circuit |
| IEC test classification |
B2 |
| C1 |
| C2 |
| C3 |
| D1 |
| Maximum continuous voltage UC |
185 V DC |
| Rated current |
≤ 380 mA (25 °C) |
| Operating effective current IC at UC |
≤ 6 µA |
| Residual current IPE |
≤ 4 µA |
| Nominal discharge current In (8/20) µs (Core-Core) |
≤ 5 kA |
| Nominal discharge current In (8/20) µs (core-earth) |
≤ 5 kA |
| Total discharge current Itotal (8/20) µs |
10 kA |
| Nominal pulse current Ian (10/700) µs (Core-Core) |
150 A |
| Nominal pulse current Ian (10/700) µs (Core-Earth) |
150 A |
| Voltage protection level Up (core-core) |
250 V (B2 - 100 A) |
| ≤ 250 V (C1 - 500 A) |
| ≤ 410 V (C2 - 5 kA) |
| Voltage protection level Up (core-ground) |
≤ 580 V (B2 - 100 A) |
| ≤ 580 V (C1 - 500 A) |
| Response time tA (core-core) |
≤ 100 ns |
| Response time tA (core-earth) |
≤ 100 ns |
| Input attenuation aE, sym. |
typ. 0.3 dB (≤ 2,8 MHz / 100 Ω) |
| typ. 3 dB (≤ 25 MHz / 100 Ω) |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system |
25 MHz |
| Capacity (core-core) |
55 pF |
| Capacity (core-earth) |
7 pF |
| Surge protection fault message |
None |
| Impulse durability (conductor-conductor) |
C1 - 1 kV/500 A |
| Impulse durability (conductor-ground) |
B2 - 4 kV/100 A |
| C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA |
| VDE requirement class |
B2 |
| C1 |
| C2 |
| C3 |
| D1 |
| Maximum continuous voltage UC |
130 V AC |
| Pulse discharge current Iimp (10/350) µs |
2.5 kA (Number of pulses category D1) |
| Nominal pulse current Ian (10/1000) µs (Core-Core) |
100 A |
| Nominal pulse current Ian (10/1000) µs (Core-Earth) |
100 A |
| Voltage protection level Up (core-core) |
≤ 250 V (C3 - 100 A) |
| Voltage protection level Up (core-ground) |
≤ 790 V (C2 - 5 kA) |
|
≤ 300 V (C3 - 100 A) |
| Resistance in series |
3.3 Ω 20 % |
| Impulse durability (conductor-conductor) |
C2 - 10 kV/5 kA |
| B2 - 4 kV/100 A |
| Impulse durability (conductor-ground) |
D1 - 1 kA |
| Standards and Regulations |
| Standards/specifications |
IEC 61643-21 2002 |
| IEC 61643-21 |
| General |
| Housing material |
Zinc die-cast |
| Color |
silver/black |
| Mounting type |
Connection-specific attachment plug and DIN rail, 35 mm |
| Design |
Attachment plug for DIN rail mounting |
| Number of positions |
4 |
| Direction of action |
Line-Line & Line-Ground/Shield |
| Standards for cearances and creepage distances |
IEC 60664-1 |
| VDE 0110-1 |
| Connection, equipotential bonding |
| Connection method |
Cable connection/DIN rail |
| Connection data |
| Connection method |
RJ45/COMBICON |
| Connection method IN |
RJ45 socket |
| Connection method OUT |
RJ45 socket |
| Connection method IN |
MC 1,5/4 |
| Connection method OUT |
MC 1,5/4 |
| Connection technology |
Screw connection |
| Screw thread |
M2 |
| Tightening torque |
0.22 Nm |
| Stripping length |
7 mm |
| Conductor cross section flexible |
0.14 mm² ... 1.5 mm² |
| Conductor cross section solid |
0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG |
28 ... 16 |
| Dimensions |
| Height |
103 mm |
| Width |
25 mm |
| Depth |
63 mm |
 |
| Environmental Product Compliance |
| Reach and RoHS Compliant |
Reach and RoHS Compliant |
| Approvals |
|
UL Listed
EAC |
| Commercial data |
| Packing unit |
1 |
| Weight per piece |
320.0 g |
| Country of origin |
Germany |