M-7018-16 - 16 Channel Analog Input, Current Input, & Thermocouple Input Data Acquisition Module. by ICP DAS
|
|
|
M-7018-16_SUMMARY.html
- 16-channel Differential Analog Input
- ±30 VDC Overvoltage Protection
- Current, Voltage or Thermocouple Input
- 3000 VDC Intra-module Isolation
- Adjustable CJC offset
- Open Thermocouple Detection
- Dual Watchdog
- Wide Operating Temperature Range: -25 to +75C
|
|
|
M-7018-16_DESCRIPTION.html
The M-7018-16 is an analog input module designed with 16 differential analog input channels. The voltage input ranges from ±15 mV to ±2.5 V, the current input range can be either +4 to +20 mA, 0 to +20 mA, or ±20 mA, and types J, K, T, E, R, S, B, N, C, L, M, LDIN43710 thermocouple can be used for the thermocouple input. Designed with overvoltage protection of up to 30 VDC is provided. M-7018-16 features per-channel open wire detection for the thermocouple input types, 4 kV ESD protection and 3000 VDC intra-module isolation.
M-7018-16.html
I/O Specifications
Channels
|
16
|
Wiring
|
Differential
|
td>
Sensor Types
Thermocouple
|
J, K, T, E, R, S, B, N, C
|
|
Voltage
|
±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V
|
|
Current
|
±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 O resistor)
|
Resolution
|
16-bit
|
Accuracy
|
0.1% of FSR
|
Sampling Rate
|
10 Hz (Total)
|
Input Impedance
|
> 400 kO
|
Common Voltage Protection
|
25 VDC
|
Individual Channel Configuration
|
-
|
Overvoltage Protection
|
±30 VDC
|
Open Wire Detection (for thermocouple only)
|
Yes
|
Temperature Outputs Consiste
|
-
|
Stable Temperature Output in the Field
|
-
|
System Specifications
Interface
|
RS-485
|
Bias Resistor
|
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.)
|
Format
|
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
|
Baud Rate
|
1200 to 115200 bps
|
Protocol
|
Modbus RTU, DCON
|
Dual Watchdog
|
Yes, Module (1.6 Seconds), Communication (Programmable)
|
System LED Indicator
|
Yes, 1 as Power/Communication Indicator
|
I/O LED Indicator
|
-
|
7-Segment LED Display
|
-
|
Intra-Module Isolation, Field-to-Logic
|
3000 VDC
|
ESD (IEC 61000-4-2)
|
±4 kV Contact for each Terminal
|
EFT (IEC 61000-4-4)
|
±4 kV to Power
|
Surge (IEC 61000-4-5)
|
±2 kV for Power Line
|
Reverse Polarity Protection
|
Yes
|
Input Range
|
+10 ~ +30 VDC
|
Consumption
|
0.5 W
|
Dimensions (L x W x H)
|
120 mm x 76 mm x 42 mm
|
Installation
|
DIN-Rail or Wall Mounting
|
Operating Temperature
|
-25 to +75C
|
Storage Temperature
|
-40 to +85C
|
Humidity
|
10 to 95% RH, Non-condensing
|
l');
?>
|
|