04032010 RPS830 Remote Power Switch R2 - * Discontinued* - 1U, 8 NEMA 5-15R plugs, 32 Amps total, 100-120 VAC by PERLE
|
|
|
- Improve administrative efficiencies with integrated multi-outlet power control, all from a single vendor
- Increase uptime
- Maintain Business Continuity
- Proactively identify and manage problems to improve mean time between failure (MTBF)
- Restore IT assets without dispatching service personnel to remote Data Centers
|
|
|
The Perle 04032010 RPS830, an intelligent power switch located near the equipment, can remotely power cycle the equipment to restore functionality resulting in decrease risks by reducing mean time to recovery (MTTR).
Integrated Management with Perle IOLAN Console Servers
When used with our IOLAN console servers, Perle Remote Power Switches form an integral part of a total Data Center management solution. Remote power management of equipment takes advantage of the extensive security such as SSH/SSL encryption, RADIUS, TACACS, Kerberos, LDAP, NIS and SecurID authentication schemes provided by IOLAN console servers.
Through a power hot-key tool on the IOLAN, administrators can power cycle equipment while they are still in their serial console session, enabling them to monitor equipment start-up messages as it is restored.
Features - Remote Power Switch
- Independent Control of Power Ports
Each AC power plug can be independently powered on, off or cycled giving complete control over when and in which sequence equipment is restored.
- Dual AC Power Bus Architecture
Perle RPS models are the only remote power switches with a dual AC Power bus architecture providing better equipment protection than single power bus systems.
When used with redundant power systems such as the Dell Poweredge 6850, Perle's Remote Power Switches are able to draw power from separate AC sources ensuring that at least one source of AC power is always up and running thereby maximizing equipment uptime.
Both power buses are protected by separate breakers. If a breaker does trip, only the associated bus will be turned off, leaving the other bus operational. Single bus power switches that come with single or dual breaker systems will shut down the entire power switch when there is a breaker-tripping event.
- Horizontal Form Factor Models with NEMA or IEC Plug standards
Perle Remote Power Switches are available in a configuration to meet your data center power needs.Various models are available in horizontal (1U or 2U) form factors as well a choice of North American NEMA or international IEC power plug standards
- Emergency Manual Power Switch
This gives an IT administrator in the vicinity the ability to power on or off the switch in an emergency. Other vendors require the unplugging of power input cords which would cause potentially dangerous arcing or having run to the main power panel to trip a breaker.
North America / Asia |
Europe |
|
|
Perle RPS830 1U (Horizontal), 8 NEMA 5-15R plugs, 100-120 VAC
Dual AC Input: Two Separate Circuits; 20 Amps Maximum per Circuit (16 Amps De-rated)
- Voltage: 100 - 120 VAC 50/60 Hz
- Connectors: Two (2) IEC-320-C20 Inlets, Line Cords Supplied
AC Outputs (plugs):
- Connectors: Eight (8) NEMA 5-15R Plugs, Split into Two 20 Amp Circuits
- Load: 16 Amps per Circuit; providing a Maximum Total of 32 Amps (De-rated)
Console / Modem Port Interface:
- Connector: RJ45 (cisco pinout), RS232C, DTE
- Coding: Serial ASCII, 8 Bits, No Parity
Physical / Environmental
- Width: 19” (48 cm) Standard Rack
- Depth: 8.7” (22 cm)
- Height: 1.75” (4.5 cm) 1 Rack U
- Weight: 10 lbs. (4.5 Kg) Shipping Weight
- Temperature: (Operating) 32°F to 122°F (0°C to 50°C)
- Humidity: 19 - 90% RH
- Power Consumption: 18 watts
- Heat Output (BTU/HR): 61
Approvals:
UL, cUL, FCC Class A, RoHS Compliant |
Perle RPS820 1U (Horizontal), 8 IEC320-C13 plugs, 200 – 240 VAC
Dual AC Input: Two Separate Circuits; 16 Amps Maximum per Circuit
- Voltage: 200 - 240 VAC 50/60 Hz
- Connectors: Two (2) IEC-320-C20 Inlets
AC Outputs (plugs):
- Connectors: Eight (8) IEC-320-C13 Plugs, Split into Two 16 Amp Circuits
- Load: 16 Amps per Circuit; providing a Maximum Total of 32 Amps.
Console / Modem Port Interface:
- Connector: RJ45 (cisco pinout), RS232C, DTE
- Coding: Serial ASCII, 8 Bits, No Parity
Physical / Environmental
- Width: 19” (48 cm) Standard Rack
- Depth: 8.7” (22 cm)
- Height: 1.75” (4.5 cm) 1 Rack U
- Weight: 10 lbs. (4.5 Kg) Shipping Weight
- Temperature: (Operating) 32°F to 122°F (0°C to 50°C)
- Humidity: 19 - 90% RH
- Power Consumption: 18 watts
- Heat Output (BTU/HR): 61
Approvals:
UL, cUL, FCC Class A, RoHS Compliant |
Perle RPS1630H 2U (Horizontal), 16 NEMA 5-15R plugs, 100-120 VAC (16 amps De-rated)
Dual AC Input: Two Separate Circuits; 16 Amps Maximum per Circuit
- Voltage: 100 - 120 VAC 50/60 Hz
- Connectors: Two (2) IEC-320-C20 Inlets, Line Cords Supplied
AC Outputs (plugs):
- Connectors: Sixteen (16) NEMA 5-15R Plugs, Split into Two 20 Amp Circuits
- Load: 16 Amps per Circuit; providing a Maximum Total of 32 Amps (De-rated)
Console / Modem Port Interface:
- Connector: RJ45 (Cisco pinout), RS232C, DTE
- Coding: Serial ASCII, 8 Bits, No Parity
Physical / Environmental
- Width: 19” (48.1 cm) Standard Rack
- Depth: 8.7” (22.1 cm)
- Height: 3.5” (8.9 cm) 2 Rack U
- Weight: 14 lbs. (6.4 Kg) Shipping Weight
- Temperature: (Operating) 32°F to 122°F (0°C to 50°C)
- Humidity: 10 - 90% RH
- Power Consumption: 20 watts
- Heat Output (BTU/HR): 68
Approvals:
UL, cUL, FCC Class A, RoHS Compliant |
Perle RPS1620H 2U (Horizontal), 16 IEC320-C13 plugs, 200 – 250 VAC
Dual AC Input: Two Separate Circuits; 16 Amps Maximum per Circuit
- Voltage: 200 - 250 VAC 50/60 Hz
- Connectors: Two (2) IEC-320-C20 Inlets
AC Outputs (plugs):
- Connectors: Sixteen (16) IEC-320-C13 Plugs, Split into Two 16 Amp Circuits
- Load: 16 Amps per Circuit; providing a Maximum Total of 32 Amps.
Console / Modem Port Interface:
- Connector: RJ45 (Cisco pinout), RS232C, DTE
- Coding: Serial ASCII, 8 Bits, No Parity
Physical / Environmental
- Width: 19” (48.1 cm) Standard Rack
- Depth: 8.7” (22.1 cm)
- Height: 3.5” (8.9 cm) 2 Rack U
- Weight: 14 lbs. (6.4 Kg) Shipping Weight
- Temperature: (Operating) 32°F to 122°F (0°C to 50°C)
- Humidity: 10 - 90% RH
- Power Consumption: 20 watts
- Heat Output (BTU/HR): 68
Approvals:
UL, cUL, FCC Class A, RoHS Compliant |
|
|
|
|