MODEL |
MDR-60-5 |
OUTPUT |
DC VOLTAGE |
5V |
RATED CURRENT |
10A |
CURRENT RANGE |
0-10A |
RATED POWER |
50W |
RIPPLE & NOISE (max.) Note.2 |
80mVp-p |
VOLTAGE ADJ. RANGE |
5 – 6V |
VOLTAGE TOLERANCE Note. 3 |
+-2.0% |
LINE REGULATION |
+-1.0% |
LOAD REGULATION |
+-1.5% |
SETUP, RISE TIME Note. 5 |
500ms, 30ms/230VAC
500ms, 30ms/115VAC at full load |
HOLD UP TIME (Typ.) |
50ms/230VAC 20ms/115VAC at full load |
INPUT
|
VOLTAGE RANCE Note. 6 |
85 - 264VAC 120 - 370VDC |
FREQUENCY RANGE |
47-63Hz |
EFFICIENCY (Typ.) |
78% |
AC CURRENT (Typ.) |
1.8A/115VAC 1A/230VAC |
INRUSH CURRENT (Typ.) |
COLD START 30A/115VAC 60A/230VAC |
LEAKAGE CURRENT |
<1mA/ 240VAC |
PROTECTION |
OVERLOAD |
105 - 150% rated output power |
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
OVER VOLTAGE |
6.25 – 7.25V |
Protection type : Shut down o/p voltage, re-power on to recover |
FUNCTION |
DC OK ACTIVE SIGNAL (max.) |
Relay contact rating(max.): 30V/1A resistive |
ENVIRONMENT |
WORKING TEMP. |
-20 to + 70 (Refer to output load derating curve) |
WORKING HUMIDITY |
20 - 90% RH non-condensing |
STORAGE TEMP., HUMIDITY |
-40 to +85 , 10 - 95% RH |
TEMP. COEFFICIENT |
+- 0.03%C (0~50C) |
VIBRATION |
Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6 |
SAFETY & EMC (Note 4) |
SAFETY STANDARDS |
UL508, TUV EN60950-1 approved, NEC class 2 / LPS compliant (24V,48V only) |
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms/500VDC 25 70%RH |
EMI CONDUCTION & RADIATION |
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B |
HARMONIC CURRENT |
Compliance to EN61000-3-2,-3 |
EMS IMMUNITY |
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A |
OTHERS |
MTBF |
299.2K hrs min. MIL-HDBK-217F (25 ) |
DIMENSION |
40*90*100mm (W*H*D) |
PACKING |
0.33Kg; 42pcs/14.8Kg/0.82CUFT |