Need assistance or guidance?

Contact us @: 1-800-301-9097
Login / Register Contact Us
 
Profi-5024 - PROFIBUS Remote I/O Module(4-Ch Isolated Analog Voltage & Current Output) by ICP DAS

Profi-5024 - PROFIBUS Remote I/O Module(4-Ch Isolated Analog Voltage & Current Output)
by ICP DAS

Write a review Write a review
PROFIBUS Remote I/O Module 4 Channel Isolated Analog Output (Voltage Output) & Current Output, supports operating temperatures from -25°C ~ +75°C (-13°F ~ +167°F).
Mfg SKU # : Profi-5024
List Price : $759.00
Our Price : $744.00
Stock : Call for Availability
Quantity :

The PROFI-5024 is specially designed for the slave device of PROFIBUS DP protocol. It supports up to 4-channel isolated analog voltage/current output with 3750Vrms field to logic isolation. Users can easily to choose and configure it by using the GSD file in any PROFIBUS Configurator.

Profi-5017

  • Industrial Automation
  • Factory Automation
  • Process Automation
  • Etc...
Protocol & Hierarchy DP-V0 Slave
Supports Transmission Rate (kbps) 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000
Transmission Rate Setting detected automatically
Address Setting 0~99 set by rotary switches
Indicators PWR and RUN LEDs
I/O modules Configuration Configured by GSD file
Network Isolation Protection High Speed iCoupler
DC Isolation Protection 3000 VDC on PROFIBUS side
4KV ESD Protection Contact for each terminal

 

 

Hardware
ESD Protection 4 kV class A
PROFIBUS Interface
Controller Profichip VPCLS2
Transceiver ADI ADM2486
Connector 9-pin female D-Sub
Baud Rate (bps) 9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M
Transmission Distance (m) Depend on baud rate (for example, max. 1200 m at 9.6 kbps )
Isolation 3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic
Protocol DP-V0
LED
Round LED PWR LED, RUN LED
Power
Power supply Unregulated +10 ~ +40 VDC
Protection Reverse polarity protection, Over-voltage brown-out protection
Power Consumption 1 W
I/O
Digital Output 24 Channels (Sink), Isolated with common ground
Load Voltage: +10 ~ +40V 
Maximum Load Current: 650mA w/ Short-Circuit Protection
Isolation Voltage: 3750Vrms
Mechanism
Installation DIN-Rail
Dimensions 91 mm x 128 mm x 52 mm (W x L x H)
Environment
Operating Temp. -25 ~ 75℃
Storage Temp. -30 ~ 85℃
Humidity 5 ~ 95% RH, non-condensing

Copyright © 2024 iComTech. All rights reserved. Shopping Cart Software powered by ecMidas.