M-7065BD - 4-ch Isolated DI (Wet, 4~30 VDC) and 5-ch DC-SSR Output Module with LED Display by ICP DAS
|
|
|
M-7065BD_SUMMARY.html
- 4 Digital Input channels and 5 DC SSR Output channels
- Form A DC Solid State Relay Output
- No Arcing, No Bounce, and No Switching Noise
- Sink- and Source-type for Digital Input
- Digital Input Channels can be used as 16-bit Counters
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- Dual Watchdog
- Wide Operating Temperature Range: -25 ~ +75C
|
|
|
M-7065BD_DESCRIPTION.html
The M-7065B provides 4 digital input channels and 5 DC SSR output channels. All digital input channels can be used as 16-bit counters. In addition, the digital input channels can be selected either as sink- or source-type via wire connections. In comparison to electromechanical relays, SSR technology provides a faster response time and greater electrical endurance. The integration of DC SSR technology also eliminates potential for arcing, bounce, and switching noise. The I-7063BD provides 11 LED indicators and the I-7065BD/M-7065BD provides 9 LED indicators that can be used to monitor the status of the digital input and SSR output. There are also options for configuring power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise protection capabilities in industrial environments. The M-7065B supports both the Modbus RTU and DCON protocols, which can be configured via software.
M-7065BD.html
CPU Module |
Watchdog Timer |
Yes, Module (1.6 Seconds), Communication (Programmable) |
Display |
Type |
I/O LED Indicator |
Isolation |
Intra-module Isolation |
3750 VDC |
EMS Protection |
EFT (IEC 61000-4-4) |
±2 kV for Power Line |
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal ±8 kV Air for Random Point |
LED Indicators |
Status |
1 x Power and Communication 9 x Digital Input/Relay Output |
Digital Input/Counter |
Channels |
4 |
Type |
Wet Contact |
Sink/Source (NPN/PNP) |
Sink/Source |
Wet Contact, ON Voltage Level |
+1 VDC Max. |
Wet Contact, OFF Voltage Level |
+4 ~ 30 VDC |
Max. Counts |
65535 (16-bit) |
Frequency |
100 Hz |
Min. Pulse Width |
5 ms |
Input Impedance |
3 kΩ |
Overvoltage Protection |
±35 VDC |
Relay Output |
Channels |
5 (Form A) |
Type |
DC-SSR |
Contact Rating |
Form A: 3 ~ 30 VDC @ 1A 5 A @ 30 VDC |
Leakage Current |
0.1 mA |
Operate Time |
1 ms |
Release Time |
1 ms |
Electrical Endurance |
Long Life, No Arcing, No Bounce, No Switching Noise |
Surge Strength |
3500 VDC |
Power on Value |
Yes |
Safe Value |
Yes |
COM Ports |
Ports |
1 x RS-485 |
Baud Rate |
1200 ~ 115200 bps |
Data Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Protocol |
Modbus RTU, DCON |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
+10 ~ +30 VDC |
Consumption |
0.6 W |
Mechanical |
Dimensions (mm) |
123 x 72 x 35 (W x L x H) |
Installation |
DIN-Rail |
Environmental |
Operating Temperature |
-25 ~ +75C |
Storage Temperature |
-40 ~ +85C |
Humidity |
10 ~ 95% RH, Non-condensing |
|
l');
?>
|