| Digital Input |
| Channels |
8 |
| Input Type |
Dry Contact: Source, Wet Contact: Sink or Source |
| Dry Contact Level |
Off Voltage Level : Open |
| On Voltage Level : Close to GND |
| Wet Contact Level |
Off Voltage Level : +4V max. |
| On Voltage Level : +10 V ~ +50 V |
| Input Impedance |
10 K Ohms, 0.5 W |
| Counters |
channels : 8 |
| Max. Counts : 16-bit (65535) |
| Max. Input Frequency : 100Hz |
| Min. Pulse Width : 5ms |
| Photo-Isolation |
3750 VDC |
| Digital Output |
| Channels |
8, Sink(NPN) |
| Output Voltage |
+3.5 ~ +50 V |
| Output Current |
700mA per channel, Direct drive power relay module |
| Intra-module Isolation, Field to Logic |
3750 VDC |
| Overvoltage Protection |
60 VDC |
| Overload Protection |
Yes |
| Short-circuit and Overcurrent Protection |
1.4 A |
| Thermal Overload trip temperature |
150 °C |
| Interface |
| Interface |
RS-485 |
| Format |
N, 8, 1 |
| Baud Rate |
1200 ~ 115200bps |
| LED Display |
| 1 LED as Power/Communication indicator |
| 8 LEDs as Digital Input indicators and 8 LEDs as Digital Output indicators (for I-7055D-NPN) |
| Power |
| Input Voltage Range |
10 ~ 30 VDC |
| Power Consumption |
1.2W (I-7055-NPN)/2.2W (I-7055D-NPN) |
| EMS Protection |
| ESD (IEC 61000-4-2) |
±4 kV Contact for each terminal,
±8 kV Air for random point |
| EFT (IEC 61000-4-4) |
±4 kV for 16DO and Power
±2 kV for RS-485 port |
| Surge (IEC 61000-4-5) |
±3 kV for power liner |
| Environment |
| Operating Temperature |
-25 ~ 75°C |
| Storage Temperature |
-40 ~ 85°C |
| Humidity |
10 ~ 95% RH, non-condensing |