I-7012D - Analog Input module with Display by ICP DAS
|
|
|
Voltage Input and Current Input Analog Input Data Acquisition Module with LED Display, 1 Analog Input, 1 Digital Input, 2 Digital Output, communicable over RS-485, and FREE EZ Data Logger Software. Supports operating temperatures between -25°C ~ +75°C (-13°F ~ +167°F).
|
|
|
I-7012 is a cost-effective solution for a wide range of valuable industrial control signals and systems. The DCON utility can help users to configure and test I-7012 modules. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals. I-7012D comes with FREE EZ Data Logger Software.
Analog Input |
Input Channels |
1 |
Input Type |
±150mV, ±500mV, ±1V, ±5V, ±10V
±20mA (requires optional external 125 ohm resistor) |
Resolution |
16-bit |
Sampling Rate |
10 Samples/ Second |
Accuracy |
±0.05% or better |
Zero Drift |
±20uV/°C |
Span Drift |
25ppm/°C |
Band Width |
5.24Hz |
Common Mode Rejection |
86dB |
Normal Mode Rejection |
100dB |
Photo-Isolation |
3750 Vrms |
Intra-module Isolation, Field to Logic |
3000 VDC |
Digital Input |
Channels |
1 |
Logic Level 0 |
+ 1V max |
Logic Level 1 |
+ 3.5V to 30V |
Max Input Frequency |
50Hz |
Min.Pulse Width |
1 mS |
Digital Output |
Channels |
2 |
Output Type |
Sink, Open Collector to 30V |
Output Load |
30mA max per channel |
Power dissipation |
300 mW |
Interface |
Interface |
RS-485 |
Format |
N, 8, 1 |
Baud Rate |
1200 ~ 115200bps |
LED Display |
1 LED |
Power/ Communication indicator |
I-7012D Versions |
4 1/2 digits |
Power |
Input |
+10 to +30 Vdc |
Power Consumption |
1.3W (i-7012) / 1.9 W (i-7012D) |
Environment |
Operating temperature |
-25°C to 75°C |
Storage temperature |
-40°C to 85°C |
Humidity |
5% to 95%, non-condensing |
|
|