ICP DAS I-87026PW - 6 channel Analog Input, 2 channel Analog Output module by ICP DAS
|
|
|
|
6-channel Analog Input, 2-channel Analog Output, 2-channel Digital Input and 2-channel Digital Output Module
|
|
|
The 87026PW is a multifunction module that includes 6 analog input channels, 2 analog output channels, 2 digital input channels, 2 digital output channels. It provides a programmable input range on all analog input (+/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V, +/-20 mA, 0 ~ 20 mA or 4 ~ 20 mA), analog outputs are 12 bit at +/-5 V, +/-10 V, 0 ~ 20 mA or 4 ~ 20 mA and all digital outputs can be set as alarm output. Each analog input can be confi gured for an individual range and provides a high overvoltage protection of 240 Vrms. Voltage and current inputs/outputs are jumper selectable.
- Multifunction (6AI, 2AO, 2DI and 2DO)
- Supports Fast Mode and Normal Mode
- Individual Channel Confi guration
- Open Wire Detection for Current Output
- Overload and Short Circuit Protection for Digital Output
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- 240 Vrms Overvoltage Protection for Voltage Input
- 70 VDC Overvoltage Protection for Digital Input
- Jumper Selectable Voltage or Current Input/Output
- Dual Watchdog
- ±4 kV Contact ESD Protection
- Wide Operating Temperature Range: -25 °C ~ +75 °C
I/O Specifications
| Analog Input |
| Input Channels |
6 (Differential) |
| Input Type |
+/-150mV, +/-500 mV, +/-1V, +/-5 V, +/-10 V +/-20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable) |
| Resolution |
Normal Mode |
16-bit |
| Fast Mode |
12-bit |
| Sampling Rate |
Normal Mode |
10 Samples/Sec. |
| Fast Mode |
60 Samples/Sec. (Total) |
| Accuracy |
Normal Mode |
+/- 0.1% |
| Fast Mode |
+/-0.5% or better |
| Band Width |
Normal Mode |
15.7 Hz |
| Fast Mode |
78.7 Hz |
| Zero Drift |
+/- 20 μV/°C |
| Span Drift |
+/- 25 ppm/°C |
| Input Impedance |
Voltage |
2 MΩ |
| Current |
125 Ω |
| Common Mode Rejection |
86 dB Min. |
| Normal Mode Rejection |
100 dB |
| Overvoltage Protection |
240 Vrms |
| Individual Channel Configuration |
Yes |
| Analog Output |
| Output Channels |
2 |
| Output Type |
+0 V ~ +5 V, +/-5 V, +0 V ~ +10 V, +/-10 V,+0 mA ~ +20 mA, +4 mA ~ +20 mA (Jumper Selectable) |
| Resolution |
12-bit |
| Accuracy |
+/-0.1% of FSR |
| Voltage Output Capability |
10 V @ 20 mA |
| Current Load Resistance |
500 Ω |
| Power-Up and Safe Value |
Yes |
| Open Wire Detection for Current Output |
Yes, Only 4 ~ 20 mA. |
| Digital Output |
| Output Channels |
2 |
| Output Type |
Isolated Open Collector (Sink) |
| Max Load Current |
700 mA/channel Max. |
| Load Voltage |
+3.5 VDC ~ +50 VDC |
| Overvoltage Protection |
60 VDC |
| Overload Protection |
Yes |
| Short Circuit Protection |
Yes |
| Power-on Value |
Yes, Programmable |
| Safe Value |
Yes, Programmable |
| Digital Input |
| Input Channels |
2 |
| Input Type |
Wet contact (Sink) |
| On Voltage Level |
+3.5 VDC ~ 50 VDC |
| Off Voltage Level |
+1 VDC Max. |
| Input Impedance |
10 KΩ, 0.66W |
| Counters |
Channels |
2 |
| Max. Count |
32-bit |
| Max. Input Frequency |
100 Hz |
| Min. Pulse Widt |
5 ms |
| Overvoltage Protection |
70 VDC |
System Specifications
| Interface |
| Interface |
RS-485 |
| Format |
N, 8, 1 |
| Baud Rate |
1200 ~ 115200 bps |
| Protocol |
DCON |
| Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
| LED Indicator/Display |
| System LED Indicator |
1 LED as Power/Communication Indicator |
| I/O LED Indicator |
16 LEDs as High/Low Alarm Signals |
| Isolation |
Intra-Module Isolation,
Field-to-Logic |
2500 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) |
4 kV Contact for Each Terminal |
| ±8 kV Air for Random Point |
| Power |
| Power Consumption |
1.8 W |
| Mechanical |
| Dimensions (W x L x H) |
30 mm x 102 mm x 115 mm |
| Environment |
| Operating Temperature |
-25 ~ +75 °C |
| Storage Temperature |
-30 ~ +80 °C |
| Humidity |
5 ~ 95% RH, Non-condensing |
|
|
|
|