Need assistance or guidance?

Contact us @: 1-800-301-9097
Login / Register Contact Us
 
ET-2254P - Ethernet I/O Module with 16-ch Universal DIO. Wide Operating Temperature Range: -25 ~ +75 C. The ET-2254 provides Dig by ICP DAS

ET-2254P - Ethernet I/O Module with 16-ch Universal DIO. Wide Operating Temperature Range: -25 ~ +75 C. The ET-2254 provides Dig
by ICP DAS

Write a review Write a review
ET-2254P_SUMMARY.html
  • Built-in Web Server
  • Support Modbus TCP/UDP Protocols
  • Powerful 32-bit MCU Handles Efficient Network Traffic
  • 2-port Ethernet Switch (LAN Bypass) for Daisy-Chain Wiring
  • Dual Watchdog
  • I/O Pair Connection (Push and Polling)
  • Supports web configuration and firmware update via Ethernet
  • 16 channels of Universal DIO
  • Provide Digital Output Maximum Load Current:
    • ET-2254: 100 mA/Channel
    • ET-2254P: 350 mA/Channel
  • LED Display to Indicate the I/O status
  • Bi-direction Universal DIO Ports under software control
  • Wide Operating Temperature Range: -25 ~ +75 C
Mfg SKU # : ET-2254P
Our Price : $349.00
Stock : Call for Availability
Quantity :
ET-2254P_DESCRIPTION.html The ET-2254P module - is an IP-based Ethernet I/O monitoring and control module. The module can be remotely controlled through a 10/100 M Ethernet network by using Modbus TCP/UDP protocol. Modbus has become a de facto standard communications protocol in industrial applications, and is now the most commonly available means of connecting industrial electronic devices. This makes the ET-2254P module being perfectly integrated with the HMI, SCADA, PLC or other software systems.
ET-2254P.html
System
CPU 32-bit ARM
Communication
Ethernet Port 2 x RJ-45, 10/100 Base-Tx, Switch Ports
Protocol Modbus TCP, Modbus UDP
Security Password and IP Filter
I/O Pair Connection

Yes (Push, Polling)

Dual Watchdog Yes, Module, Communication (Programmable)
LAN Bypass Yes
LED Indicators
For System Running Yes
For Ethernet Link/Ack Yes
For DI/DO status Yes
Output Capability 100 mA/+30 V for one channel @ 100% duty
2-way Isolation
Ethernet 1500 VDC
I/O 3750 VDC
EMS Protection
ESD (IEC 61000-4-2) ±8 kV Contact for Each Terminal and ±16 kV Air for Random Point
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge (IEC 61000-4-5) ±3 kV for Power Line
Power Requirements
Reverse Polarity Protection Yes
Powered from Terminal Block +10 ~ +30 VDC
Consumption 3.3 W (Max.)
Mechanical
Dimensions (L x W x H) 127 mm x 33 mm x 99 mm
Installation DIN-Rail or Wall mounting
Model ET-2254
I/O Type By Wire Connection, Configurable Universal DIO
I/O Channels 16
Digital Input
Type Dry Contact
Sink/Source (NPN/PNP) Source
On Voltage Level Close to GND
Off Voltage Level Open
Input Impedance 7.5 kO, 1 W
Digital Input Max. Count 4,294,967,295 (32-bit)
Max. Input Frequency 2.5 kHz
Programmable Digital Filter 1 ~ 6500 ms (0.08 Hz ~ 500 Hz)
Digital Output
Type Open-collector (Sink)
Sink/Source (NPN/PNP) Sink
Max. Load Current 350 mA/channel
Load Voltage +5 VDC to +50 VDC
Short Circuit Protection Yes
Power-on Value Yes, Configurable
Safe Value Yes, Configurable

l'); ?>