M-7017mC-16 - 16 Channel Current Input Module and Data Logger. Stores up to 100,000 Records. Communicable over Modbus RTU. by ICP DAS
|
|
|
M-7017mC-16_SUMMARY.html
- 16-channel Current Input
- Jumper Selectable Differential or Single-ended Wiring
- 16-bit Resolution
- Adjustable Sampling Rate
- Storage for up to 100,000 Records from16-channel Current Input
- Built-in Resistor to Simplify Current Measurement
- 110 VDC Overvoltage Protection
- 4 kV ESD and EFT Protecton
- 2 kV Surge Protection
- Dual Watchdog
- 3000 VDC Intra-module Isolation
- Wide Operating Temperature Range: -25 to +75C
|
|
|
M-7017mC-16_DESCRIPTION.html
The M-7017mC-16 is equipped with 16-channel current inputs, designed to measure current. Its user-friendly design saves both time and effort when measuring current with its built-in resistors, allowing to measure current directly without needing to add an external resistor. The module also provides 4 kV ESD protection and 110 VDC overvoltage protection for the current input, and features 3000 VDC intra-module isolation and open wire detection for 4 ~ 20 mA input. The sampling rate on the M-7017mC-16 is adjustable, allowing either fast mode or normal mode. The M-7017mC-16 comes with a data logger to record current input from all 16 channels, including date and time stamps, and stores up to 100,000 downloadable records
M-7017mC-16.html
Interface
|
RS-485
|
Bias Resistor
|
Yes, 1k? bias resistor by Jumper selectable
|
Format
|
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
|
Baud Rate
|
1200 to 115200 bps
|
Protocol
|
Modbus RTU, DCON
|
Dual Watchdog
|
Yes, Module (1.6 Seconds), Communication (Programmable)
|
System LED Indicator
|
Yes, 1 as Power/Communication Indicator
|
I/O LED Indicator
|
-
|
7-Segment LED Display
|
-
|
Intra-Module Isolation, Field-to-Logic
|
3000 VDC
|
ESD (IEC 61000-4-2)
|
±4 kV Contact for each Terminal
|
EFT (IEC 61000-4-4)
|
±4 kV to Power
|
Surge (IEC 61000-4-5)
|
±2 kV for Power Line
|
Reverse Polarity Protection
|
Yes
|
Input Range
|
+10 ~ +48 VDC
|
Consumption
|
0.6 W
|
Dimensions (L x W x H)
|
120 mm x 76 mm x 42 mm
|
Installation
|
DIN-Rail or Wall Mounting
|
Operating Temperature
|
-25 to +75C
|
Storage Temperature
|
-40 to +85C
|
Humidity
|
10 to 95% RH, Non-condensing
|
I/O Specifications
Channels
|
16
|
Wiring
|
Differential or Single-ended Wiring (Jumper Selectable)
|
Types
|
±20 mA, 0 ~ +20 mA, +4 ~ +20 mA
|
Resolution
|
16-bit
|
Sampling Rate
|
Normal Mode
|
10 Hz total
|
|
Fast Mode
|
200 Hz total
|
Accuracy
|
Normal Mode
|
+/-0.1%
|
|
Fast Mode
|
+/-0.5%
|
Zero Drift
|
+/-20 uV/C
|
Span Drift
|
+/-25 ppm/C
|
Common Voltage Protection
|
25 VDC
|
Individual Channel Configuration
|
Yes
|
Overvoltage Protection
|
110 VDC
|
Overcurrent Protection
|
Yes, 50 mA at 110 VDC
|
Virtual Channel to Channel Isolation
|
-
|
Open Wire Detection for 4 ~ 20 mA
|
Yes
|
Real Time Clock
|
Yes
|
Data Logger
|
Yes, up to 100,000 records from 16 current input channels
|
|
l');
?>
|