ICP DAS I-7012 - Analog Input module by ICP DAS
|
|
|
|
Voltage Input, Current Input, and Analog Input Data Acquisition Module with 1 Analog, 1 Digital input, 2 Digital Output, communicable over RS-485, and FREE EZ Data Logger Software. Supports operating temperatures between -25 to 75°C.
|
|
|
I-7012 is a cost-effective solution for a wide range of valuable industrial control signals and systems. The DCON utility can help users to configure and test I-7012 modules. Plenty of library functions and demo programs are provided to let users develop programs easily under Windows, Linux and DOS operating systems. Users may mount the modules on a DIN rail, panel or wall. Modules have a screw-terminal block to connect to the signals. I-7012 comes with FREE EZ Data Logger Software.

| Analog Input |
| Input Channels |
1 |
| Input Type |
±150mV, ±500mV, ±1V, ±5V, ±10V
±20mA (requires optional external 125 ohm resistor) |
| Resolution |
16-bit |
| Sampling Rate |
10 Samples/ Second |
| Accuracy |
±0.05% or better |
| Zero Drift |
±20uV/°C |
| Span Drift |
25ppm/°C |
| Band Width |
5.24Hz |
| Common Mode Rejection |
86dB |
| Normal Mode Rejection |
100dB |
| Photo-Isolation |
3750 Vrms |
| Intra-module Isolation, Field to Logic |
3000 VDC |
| Digital Input |
| Channels |
1 |
| Logic Level 0 |
+ 1V max |
| Logic Level 1 |
+ 3.5V to 30V |
| Max Input Frequency |
50Hz |
| Min.Pulse Width |
1 mS |
| Digital Output |
| Channels |
2 |
| Output Type |
Sink, Open Collector to 30V |
| Output Load |
30mA max per channel |
| Power dissipation |
300 mW |
| Interface |
| Interface |
RS-485 |
| Format |
N, 8, 1 |
| Buad Rate |
1200 ~ 115200bps |
| LED Display |
| 1 LED |
Power/ Communication indicator |
| I-7012D Versions |
4 1/2 digits |
| Power |
| Input |
+10 to +30 Vdc |
| Power Consumption |
1.3W (i-7012) / 1.9 W (i-7012D) |
| Environment |
| Operating temperature |
-25°C to 75°C |
| Storage temperature |
-40°C to 85°C |
| Humidity |
5% to 95%, non-condensing |
|
|