				6-channel Analog Input, 2-channel Analog Output, 2-channel Digital Input and 2-channel Digital Output Module
					| ICP DAS I-87026PW - 6 channel Analog Input, 2 channel Analog Output moduleby  ICP DAS
 |  |  |  
					|  |  |  |  |  |  
    | 
	
		
		
The 87026PW is a multifunction module that includes 6 analog input channels, 2 analog output channels, 2 digital input channels, 2 digital output channels. It provides a programmable input range on all analog input (+/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V, +/-20 mA, 0 ~ 20 mA or 4 ~ 20 mA), analog outputs are 12 bit at +/-5 V, +/-10 V, 0 ~ 20 mA or 4 ~ 20 mA and all digital outputs can be set as alarm output. Each analog input can be confi gured for an individual range and provides a high overvoltage protection of 240 Vrms. Voltage and current inputs/outputs are jumper selectable. 
  Multifunction (6AI, 2AO, 2DI and 2DO)Supports Fast Mode and Normal ModeIndividual Channel Confi gurationOpen Wire Detection for Current OutputOverload and Short Circuit Protection for Digital OutputConfigurable Power-on Value SettingsConfigurable Safe Value Settings240 Vrms Overvoltage Protection for Voltage Input70 VDC Overvoltage Protection for Digital InputJumper Selectable Voltage or Current Input/OutputDual Watchdog±4 kV Contact ESD ProtectionWide Operating Temperature Range: -25 °C ~ +75 °C 
I/O Specifications
  
    
      | Analog Input |  
      | Input Channels | 6 (Differential) |  
      | Input Type | +/-150mV, +/-500 mV, +/-1V, +/-5 V, +/-10 V +/-20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Jumper Selectable) |  
      | Resolution | Normal Mode | 16-bit |  
      | Fast Mode | 12-bit |  
      | Sampling Rate | Normal Mode | 10 Samples/Sec. |  
      | Fast Mode | 60 Samples/Sec. (Total) |  
      | Accuracy | Normal Mode | +/- 0.1% |  
      | Fast Mode | +/-0.5% or better |  
      | Band Width | Normal Mode | 15.7 Hz |  
      | Fast Mode | 78.7 Hz |  
      | Zero Drift | +/- 20 μV/°C |  
      | Span Drift | +/- 25 ppm/°C |  
      | Input Impedance | Voltage | 2 MΩ |  
      | Current | 125 Ω |  
      | Common Mode Rejection | 86 dB Min. |  
      | Normal Mode Rejection | 100 dB |  
      | Overvoltage Protection | 240 Vrms |  
      | Individual Channel Configuration | Yes |  
      | Analog Output |  
      | Output Channels | 2 |  
      | Output Type | +0 V ~ +5 V, +/-5 V, +0 V ~ +10 V, +/-10 V,+0 mA ~ +20 mA, +4 mA ~ +20 mA (Jumper Selectable) |  
      | Resolution | 12-bit |  
      | Accuracy | +/-0.1% of FSR |  
      | Voltage Output Capability | 10 V @ 20 mA |  
      | Current Load Resistance | 500 Ω |  
      | Power-Up and Safe Value | Yes |  
      | Open Wire Detection for Current Output | Yes, Only 4 ~ 20 mA. |  
      | Digital Output |  
      | Output Channels | 2 |  
      | Output Type | Isolated Open Collector (Sink) |  
      | Max Load Current | 700 mA/channel Max. |  
      | Load Voltage | +3.5 VDC ~ +50 VDC |  
      | Overvoltage Protection | 60 VDC |  
      | Overload Protection | Yes |  
      | Short Circuit Protection | Yes |  
      | Power-on Value | Yes, Programmable |  
      | Safe Value | Yes, Programmable |  
      | Digital Input |  
      | Input Channels | 2 |  
      | Input Type | Wet contact (Sink) |  
      | On Voltage Level | +3.5 VDC ~ 50 VDC |  
      | Off Voltage Level | +1 VDC Max. |  
      | Input Impedance | 10 KΩ, 0.66W |  
      | Counters | Channels | 2 |  
      | Max. Count | 32-bit |  
      | Max. Input Frequency | 100 Hz |  
      | Min. Pulse Widt | 5 ms |  
      | Overvoltage Protection | 70 VDC |  System Specifications
  
    
      | Interface |  
      | Interface | RS-485 |  
      | Format | N, 8, 1 |  
      | Baud Rate | 1200 ~ 115200 bps |  
      | Protocol | DCON |  
      | Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |  
      | LED Indicator/Display |  
      | System LED Indicator | 1 LED as Power/Communication Indicator |  
      | I/O LED Indicator | 16 LEDs as High/Low Alarm Signals |  
      | Isolation |  
      | Intra-Module Isolation, Field-to-Logic
 | 2500 VDC |  
      | EMS Protection |  
      | ESD (IEC 61000-4-2) | 4 kV Contact for Each Terminal |  
      | ±8 kV Air for Random Point |  
      | Power |  
      | Power Consumption | 1.8 W |  
      | Mechanical |  
      | Dimensions (W x L x H) | 30 mm x 102 mm x 115 mm |  
      | Environment |  
      | Operating Temperature | -25 ~ +75 °C |  
      | Storage Temperature | -30 ~ +80 °C |  
      | Humidity | 5 ~ 95% RH, Non-condensing |  |  
    |  |  
    |  |  
 |