86M-1620D-T - 16 DIs, sink/source, 24-110 VDC, channel LED, -40 to 75 Degree C by MOXA
|
|
|
- 16 Digital Inputs
- 24 to 110 VDC
- Channel LED
- Sink type
|
|
|
Moxa’s 86M series modules with ch-to-ch isolated DIs, ch-to-ch isolated DOs,
relays, and AOs provide more I/O options for the ioPAC 8600 series. Combined
with 85M modules, enough options are now available to allow users to select the
best I/O combination for their target application. All 86M modules are designed
for railway industry applications, and as such are compliant with EN 50121-3-2,
EN 50121-4, and EN 50155. In addition, the modules support a wide operating
temperature range of -40 to 75°C.
86M-1620D-T: 16 digital inputs, 24 to 110 VDC, channel LED, sink type
86M-1620D-T
Specifications |
• Inputs
and Outputs |
Digital Inputs |
16 channels |
Isolation |
To system:
3k VDC or 2k Vrms |
• Digital
Input |
Type |
PNP |
I/O mode |
DI |
Logic Definition |
• On: channel voltage > 0.3 x (external power voltage)
• Off: channel voltage < 0.15 x (external power voltage) |
Scan Period |
8 ms (typ.) |
Scan on Time |
0.5 ms |
Debouncing Function |
Software disable/enable |
Debouncing Time |
1 to 15 ms (software-selectable) |
Common Type |
8 points per COM |
• Physical
Characteristics |
Wiring |
I/O cable, 16 AWG (max.) |
Connector |
Spring-type terminal block |
Channel LED |
Yes |
• Environmental
Limits |
Operating Temperature |
-40 to 75°C (-40 to 176°F) |
• Power
Requirements |
Input Current |
12.6 mA @ 24 VDC |
• MTBF
(mean time between failures) |
Time |
1,115,244 hrs |
Standard |
Telcordia SR332 |
|
Common Specifications |
• Power
Requirements |
Input Voltage |
24 to 110 VDC (16.8 to 154 VDC) |
• Environmental
Limits |
Operating Temperature |
-40 to 75°C (-40 to 176°F) |
Storage Temperature |
-40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity |
5 to 95% (non-condensing) |
Shock |
IEC 60068-2-27 |
Vibration |
IEC 60068-2-6 |
• Standards
and Certifications |
Safety |
UL 508 |
EMC |
EN 55022/24 |
EMI |
FCC Part 15 Subpart B Class A, CISPR 22 |
EMS |
IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS:
80 MHz to 1000 MHz: 3 V/m
1400 MHz to 2100 MHz: 3 V/m
2100 MHz to 2700 MHz: 1 V/m
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-5 Surge: Power: 2 kV (L-PE), 1 kV (L-L); |
Rail Traffic |
EN 50155 (essential compliance*), EN 50121-3-2, EN 50121-4
*Moxa defines “essential
compliance” to include those EN 50155 requirements that make products
more suitable for rolling stock railway applications. |
• Warranty |
Warranty Period |
5 years |
|
|
|
|