Need assistance or guidance?

Contact us @: 1-800-301-9097
Login / Register Contact Us
 
29031598 TRIO-PS-2G/1AC/48DC/5 Power Supply - TRIO supply for DIN rail mounting by PERLE

29031598 TRIO-PS-2G/1AC/48DC/5 Power Supply - TRIO supply for DIN rail mounting
by PERLE

Write a review Write a review
  • 48 DC Output Voltage
  • 5 Amps
  • 240 Watts
  • Single phase AC or DC Input
  • Input Voltage Range: 85 ... 264 V AC and 99 ... 275 V DC

 

Mfg SKU # : 29031598
List Price : $288.00
Our Price : $260.00
Stock : 3
Quantity :

29031598 TRIO-PS-2G/1AC/48DC/5 Power Supply of the TRIO-PS-2G/1AC/48DC/5 Industrial Power Supply is a rugged AC to DC and DC to DC Converter built to meet the high stability and efficiency expectations of industrial, machine automation and process control environments. This Switching (switch mode) Power Supply ensures a regulated output voltage even in the event of voltage fluctuations in the power supply network. With all required safety certifications to support ITE (Information Technology Equipment), ruggedized packaging, extended operating temperatures, high peak load capabilities and high isolation voltages, TRIO Industrial Power Supply is designed to meet the needs of your industrial application.

150% Dynamic Power Boost

Dynamic Power Boost image

The dynamic boost provides additional power for starting difficult loads. By supplying up to 150% of the nominal current for 5 seconds, the TRIO-PS-2G/1AC/48DC/5 power supply starts difficult loads reliably.

36 to 55 V DC Adjustable Output Voltage Range

Using the rotary potentiometer on the front face of the TRIO-PS-2G/1AC/48DC/5 power supply, the output voltage can be optimally adjusted to meet specific application environment requirements. For example, you can easily adjust to compensate for a voltage drop caused by a long cable length.

Industrial operating temperature of -25°C to +70°C with reliable device start-up at -40°C

Equipment found in traffic management, oil and gas pipelines, weather tracking, industrial and outdoor applications must function in temperatures that cannot be supported by a commercial power supplies. With an operating temperature of -25°C to +70°C and reliable device start-up at -40°C, the TRIO-PS-2G/1AC/48DC/5 Industrial Power Supply is ideal for use with equipment subjected to harsh environments and severe temperatures.

High efficiency and low no load power consumption

Compared with other products on the market, the TRIO Industrial Power Supply provides excellent energy savings. With a very low no load power consumption and high efficiency at nominal load, just a small amount of electrical energy is converted into undesired heat energy making these very ECO friendly power supplies.

Easy & efficient installation

Installation image

The tool-free Push-in connection will save time and make installation quick and easy. And, the DIN Rail mount narrow housing will save space in the control cabinet.

Ideal application environments for a TRIO-PS-2G DIN Rail Power Supply

  • machine building
  • automated production process
  • industrial control, automation, assembly, and test equipment
  • building control, security and surveillance, and climate control systems.
  • power countless industrial automation devices such as sensors, controllers and valves

Other reasons to choose this TRIO-PS-2G Industrial Power Supply

  • Contact signal output and LED indicator for voltage out failure: If the output voltage is below the operational range, the LED turns off and the contact opens.
  • Vibration resistance up to 4 kg
  • Shock resistance up to 30g
  • Voltage Isolation input/output: 3 kV AC
  • Protections: Short-circuit, Overload, Over voltage, Over-temperature
  • High MTBF (Mean Time Between Failure) values of more than 1 million hours at +40°C ensure maximum availability
Environmental Product Compliance
REACH SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
General
Net weight 0.9 kg
Efficiency typ. 90.5 % (120 V AC)
typ. 91 % (230 V AC)
Insulation voltage input/output 3 kV AC (type test)
1.5 kV AC (routine test)
Protection class I (in closed control cabinet)
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 2000000 h (25 °C)
> 1200000 h (40 °C)
> 620000 h (60 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission EN 55011 (EN 55022)
Noise immunity Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m (Test Level 2)
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-6-3
EN 61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Conducted noise emission EN 55016 EN 61000-6-4 (Class A)
Standards/regulations EN 61000-4-11
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) DNV GL CG-0339 / Class B 2 Hz - 100 Hz resonance search, 90 min. in resonance, 2 Hz - 25 Hz, ±1.6 mm amplitude, 25 Hz - 100 Hz, 4g acceleration
Rail applications EN 50121-4
Overvoltage category (EN 60950-1) II
Overvoltage category (EN 62477-1) III
Connection data, input
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 10 mm
Output data
Nominal output voltage 48 V DC ±1 %
Setting range of the output voltage (USet) 36 V DC ... 55 V DC (> 48 V DC, constant capacity restricted)
Nominal output current (IN) 5 A
Dynamic Boost (IDyn.Boost) 7.5 A (5 s)
Derating > 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback resistance ≤ 60 V DC
Protection against surge voltage on the output ≤ 60 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP (with nominal values)
Output power 240 W
Peak switching voltages nominal load < 15 mVPP
Maximum power dissipation in no-load condition typ. 4 W (120 V AC)
typ. 4.1 W (230 V AC)
Power loss nominal load max. typ. 24.5 W (120 V AC)
typ. 20.1 W (230 V AC)
Short-circuit current < 7 A DC (Permanent)
Connection data for signaling
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Dimensions
Width 42 mm
Height 130 mm
Depth 160 mm
Weight per piece 1120.0 GRM
Input data
Nominal input voltage range 100 V AC ... 240 V AC
110 V DC ... 250 V DC
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
110 V DC ... 250 V DC ±10 %
Dielectric strength maximum ≤ 300 V AC 15 s
AC frequency range 50 Hz ... 60 Hz ±10 %
Discharge current to PE < 3.5 mA
Current consumption 2.9 A (100 V AC)
2.3 A (120 V AC)
1.2 A (230 V AC)
1.2 A (240 V AC)
Nominal power consumption 285.7 VA
Mains buffering typ. 15 ms (120 V AC)
typ. 15 ms (230 V AC)
Input fuse 6.3 A (internal (device protection))
Choice of suitable circuit breakers 6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.91
Connection data, onput
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 8 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Approvals
 
  • cULus Listed
  • cULus Recognized
  • EAC
  • UL Recognized
  • cUL Recognized
  • cUL Listed
  • UL Listed

Copyright © 2024 iComTech. All rights reserved. Shopping Cart Software powered by ecMidas.