Need assistance or guidance?

Contact us @: 1-800-301-9097
Login / Register Contact Us
 
29031558 TRIO-PS-2G/3AC/24DC/20 Power Supply - TRIO power supply with push-in connection for DIN rail mounting by PERLE

29031558 TRIO-PS-2G/3AC/24DC/20 Power Supply - TRIO power supply with push-in connection for DIN rail mounting
by PERLE

Write a review Write a review
  • 24V DC Output Voltage
  • Output Amps: 5, 10, 20, or 40 Amps
  • Output Watts: 120, 240, 480, or 960 W
  • 3-phase AC Input Voltage Range: 320 to 575 V AC
  • 2-phase AC Input Voltage Range: 360 to 575 V AC

 

Mfg SKU # : 29031558
List Price : $462.00
Our Price : $416.00
Stock : 3
Quantity :

29031558 TRIO-PS-2G/3AC/24DC/20 Power Supply of the TRIO 3-Phase Power Supplies offer a complete range of rugged AC to DC Converters built to meet the high stability and efficiency expectations of industrial, machine automation and process control environments. These Switch Mode Power Supplies ensure a regulated output voltage even in the event of voltage fluctuations in the power supply network. With all required safety certifications to support ITE (Information Technology Equipment), ruggedized packaging, extended operating temperatures, high peak load capabilities and high isolation voltages, TRIO 3-Phase Power Supplies are designed to meet the needs of your high power industrial application.

150% Dynamic Power Boost

Dynamic Power Boost image

The dynamic boost provides additional power for starting difficult loads. By supplying up to 150% of the nominal current for 5 seconds TRIO power supplies start difficult loads reliably.

24 to 28 V DC Adjustable Output Voltage Range

Using the rotary potentiometer on the front face of the TRIO power supply, the output voltage can be optimally adjusted to meet specific application environment requirements. For example, you can easily adjust to compensate for a voltage drop caused by a long cable length.

Industrial operating temperature of -25°C to +70°C

Equipment found in traffic management, oil and gas pipelines, weather tracking, industrial and outdoor applications must function in temperatures that cannot be supported by a commercial power supplies. With an operating temperature of -25°C to +70°C, the TRIO 3-Phase Power Supply is ideal for use with equipment subjected to harsh environments and severe temperatures. Some models even guarantee reliable device start-up at -40°C.

High efficiency and low no load power consumption

Compared with other products on the market, the TRIO 3-Phase Power Supply provides excellent energy savings. With a very low no load power consumption and over high efficiency at nominal load, just a small amount of electrical energy is converted into undesired heat energy making these very ECO friendly power supplies.

Easy & efficient installation

Installation image

The tool-free Push-in connection will save time and make installation quick and easy. And, the DIN Rail mount narrow housing will save space in the control cabinet.

Ideal application environments for a TRIO DIN Rail Power Supply

  • drive motors and other devices
  • machine building
  • automated production process
  • industrial control, automation, assembly, and test equipment
  • building control, security and surveillance, and climate control systems.
  • power countless industrial automation devices such as sensors, controllers and valves

Other reasons to choose a TRIO Industrial Power Supply

  • Contact signal output and LED indicator for voltage out failure: If the output voltage is below the operational range, the LED turns off and the contact opens.
  • Vibration resistance up to 4 kg
  • Shock resistance up to 30g
  • Voltage Isolation input/output: 3 kV AC
  • Protections: Short-circuit, Overload, Over voltage, Over-temperature
  • High MTBF (Mean Time Between Failure) values of more than 1 million hours at +40°C ensure maximum availability
TRIO-PS-2G/3AC/24DC/5 - 29031538 TRIO-PS-2G/3AC/24DC/10 - 29031548 TRIO-PS-2G/3AC/24DC/20 - 29031558 TRIO-PS-2G/3AC/24DC/40 - 29031568
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 25; Environmentally Friendly Use Period = 25; Environmentally Friendly Use Period = 25; Environmentally Friendly Use Period = 25;
REACH SVHC Lead 7439-92-1 Lead 7439-92-1
General
Net weight 0.4 kg 0.9 kg 1.5 kg 2.6 kg
Efficiency > 91 % (at 400 V AC and nominal values) > 92 % (at 400 V AC and nominal values) > 93 % (400 V AC) typ. 93 % (400 V AC)
Insulation voltage input/output 3 kV AC (type test) 3 kV AC (type test) 3 kV AC (type test) 3 kV AC (type test)
1.5 kV AC (routine test) 1.5 kV AC (routine test) 1.5 kV AC (routine test) 1.5 kV AC (routine test)
Protection class II (in closed control cabinet) I (in closed control cabinet) I (in closed control cabinet) I (in closed control cabinet)
Degree of protection IP20 IP20 IP20 IP20
MTBF (IEC 61709, SN 29500) > 2300000 h (25 °C) > 2100000 h (25 °C) > 1800000 h (25 °C) > 1730000 h (25 °C)
> 1300000 h (40 °C) > 1200000 h (40 °C) > 1100000 h (40 °C) > 1051000 h (40 °C)
> 620000 h (60 °C) > 590000 h (60 °C) > 510000 h (60 °C) > 510000 h (60 °C)
Mounting position horizontal DIN rail NS 35, EN 60715 horizontal DIN rail NS 35, EN 60715 horizontal DIN rail NS 35, EN 60715 horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Efficiency 500 V AC typ. 93.3 % (480 V AC)
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU Conformance with EMC Directive 2014/30/EU Conformance with EMC Directive 2014/30/EU Conformance with EMC Directive 2014/30/EU
Noise emission EN 55011 (EN 55022) EN 55011 (EN 55022) EN 55011 (EN 55022) EN 55011 (EN 55022)
Noise immunity Immunity according to EN 61000-6-2 (industrial) Immunity according to EN 61000-6-2 (industrial) Immunity according to EN 61000-6-2 (industrial) Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
Standards/regulations EN 61000-4-2 EN 61000-4-2 EN 61000-4-2 EN 61000-4-2
Contact discharge 4 kV (Test Level 2) 4 kV (Test Level 2) 4 kV (Test Level 2) 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3 EN 61000-4-3 EN 61000-4-3 EN 61000-4-3
Frequency range 80 MHz ... 1 GHz 80 MHz ... 1 GHz 80 MHz ... 1 GHz 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3) 10 V/m (Test Level 3) 10 V/m (Test Level 3) 10 V/m (Test Level 3)
Frequency range 1.4 GHz ... 2 GHz 1.4 GHz ... 2 GHz 1.4 GHz ... 2 GHz 1.4 GHz ... 2 GHz
Test field strength 3 V/m (Test Level 2) 3 V/m (Test Level 2) 3 V/m (Test Level 2) 3 V/m (Test Level 2)
Standards/regulations EN 61000-4-4 EN 61000-4-4 EN 61000-4-4 EN 61000-4-4
Comments Criterion B Criterion B Criterion B Criterion B
Standards/regulations EN 61000-6-3 EN 61000-6-3 EN 61000-6-3 EN 61000-6-3
EN 61000-4-6 EN 61000-4-6 EN 61000-4-6 EN 61000-4-6
Frequency range 0.15 MHz ... 80 MHz 0.15 MHz ... 80 MHz 0.15 MHz ... 80 MHz 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3) 10 V (Test Level 3) 10 V (Test Level 3) 10 V (Test Level 3)
Conducted noise emission EN 55016 EN 61000-6-4 (Class A) EN 55016 EN 61000-6-4 (Class A) EN 55016 EN 61000-6-4 (Class A) EN 55016 EN 61000-6-4 (Class A)
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC Conformance with Low Voltage Directive 2014/35/EC Conformance with Low Voltage Directive 2014/35/EC Conformance with Low Voltage Directive 2014/35/EC
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only) EN 61558-2-16 (air clearances and creepage distances only) EN 61558-2-16 (air clearances and creepage distances only)
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV) IEC 60950-1/VDE 0805 (SELV) IEC 60950-1/VDE 0805 (SELV) IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV) EN 50178/VDE 0160 (PELV) EN 50178/VDE 0160 (PELV) EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV) IEC 60950-1 (SELV) and EN 60204-1 (PELV) IEC 60950-1 (SELV) and EN 60204-1 (PELV) IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410 DIN VDE 0100-410 DIN VDE 0100-410 DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2 EN 61000-3-2 EN 61000-3-2 EN 61000-3-2
UL approvals UL Listed UL 508 UL Listed UL 508 UL Listed UL 508 UL Listed UL 508
UL/C-UL Recognized UL 60950-1 UL/C-UL Recognized UL 60950-1 UL/C-UL Recognized UL 60950-1 UL/C-UL Recognized UL 60950-1
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27) 18 ms, 30g, in each space direction (according to IEC 60068-2-27) 18 ms, 30g, in each space direction (according to IEC 60068-2-27) 11 ms, 15g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) DNV GL CG-0339 / Class B 2 Hz - 100 Hz resonance search, 90 min. in resonance, 2 Hz - 13.2 Hz, ±1 mm amplitude, 13.2 Hz - 100 Hz, 0.7g acceleration
15 Hz ... 150 Hz, 4g, 90 min. 15 Hz ... 150 Hz, 4g, 90 min. 15 Hz ... 150 Hz, 4g, 90 min.
Rail applications EN 50121-4 EN 50121-4 EN 50121-4 EN 50121-4
Shipbuilding approval GL applied for
Standards/regulations EN 61000-4-11
Overvoltage category (EN 60950-1) II
Overvoltage category (EN 62477-1) III
Connection data, input
Connection method Push-in connection Push-in connection Push-in connection Push-in connection
Conductor cross section solid min. 0.2 mm² 0.2 mm² 0.2 mm² 0.2 mm²
Conductor cross section solid max. 4 mm² 4 mm² 4 mm² 4 mm²
Conductor cross section flexible min. 0.2 mm² 0.2 mm² 0.2 mm² 0.2 mm²
Conductor cross section flexible max. 2.5 mm² 2.5 mm² 2.5 mm² 2.5 mm²
Conductor cross section AWG min. 24 24 24 24
Conductor cross section AWG max. 12 12 12 12
Stripping length 10 mm 10 mm 10 mm 10 mm
Output data
Nominal output voltage 24 V DC ±1 % 24 V DC ±1 % 24 V DC ±1 % 24 V DC ±1 %
Setting range of the output voltage (USet) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 5 A 10 A 20 A 40 A
Dynamic Boost (IDyn.Boost) 7.5 A (5 s) 15 A (5 s) 30 A (5 s) 60 A (5 s)
Derating > 60 °C ... 70 °C (2.5%/K) > 60 °C ... 70 °C (2.5%/K) > 60 °C ... 70 °C (2.5%/K) > 60 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity Yes, for redundancy and increased capacity Yes, for redundancy and increased capacity Yes, for redundancy and increased capacity
Connection in series yes yes yes yes
Protection against surge voltage on the output ≤ 30 V DC ≤ 30 V DC ≤ 30 V DC ≤ 30 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %) < 1 % (change in load, static 10 % ... 90 %) < 1 % (change in load, static 10 % ... 90 %) < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %) < 0.1 % (change in input voltage ±10 %) < 0.1 % (change in input voltage ±10 %) < 0.1 % (change in input voltage ±10 %)
Residual ripple ≤ 20 mVPP ≤ 20 mVPP ≤ 20 mVPP ≤ 50 mVPP
Output power 120 W 240 W 480 W 960 W
Typical response time < 1 s < 1 s < 1 s < 1 s
Maximum power dissipation in no-load condition < 1 W (400 V AC) < 1.1 W (400 V AC) < 1.2 W (400 V AC) < 14 W (400 V AC)
Power loss nominal load max. < 12 W (480 V AC) < 22 W (480 V AC) < 38 W (480 V AC) < 68 W (480 V AC)
Feedback resistance < 35 V
Short-circuit current < (Permanent)
Connection data for signaling
Connection method Push-in connection Push-in connection Push-in connection Push-in connection
Conductor cross section solid min. 0.2 mm² 0.2 mm² 0.2 mm² 0.2 mm²
Conductor cross section solid max. 1.5 mm² 1.5 mm² 1.5 mm² 1.5 mm²
Conductor cross section flexible min. 0.2 mm² 0.2 mm² 0.2 mm² 0.2 mm²
Conductor cross section flexible max. 1.5 mm² 1.5 mm² 1.5 mm² 1.5 mm²
Conductor cross section AWG min. 24 24 24 24
Conductor cross section AWG max. 16 16 16 16
Stripping length 8 mm 8 mm 8 mm 8 mm
Dimensions
Width 35 mm 42 mm 65 mm 110 mm
Height 130 mm 130 mm 130 mm 130 mm
Depth 115 mm 160 mm 160 mm 160 mm
Weight per piece 568.5 GRM 1070.0 GRM 1717.0 GRM 2850.0 GRM
Input data
Nominal input voltage range 3x 400 V AC ... 500 V AC 3x 400 V AC ... 500 V AC 3x 400 V AC ... 500 V AC 3x 400 V AC ... 500 V AC
2x 400 V AC ... 500 V AC 2x 400 V AC ... 500 V AC 2x 400 V AC ... 500 V AC
Input voltage range 3x 400 V AC ... 500 V AC -20 % ....+15 % 3x 400 V AC ... 500 V AC -20 % ....+15 % 3x 400 V AC ... 500 V AC -20 % ....+15 % 3x 400 V AC ... 500 V AC -20 % ....+15 %
2x 400 V AC ... 500 V AC -10 % ... +15 % 2x 400 V AC ... 500 V AC -10 % ... +15 % 2x 400 V AC ... 500 V AC -10 % ... +15 %
AC frequency range 50 Hz ... 60 Hz 50 Hz ... 60 Hz 50 Hz ... 60 Hz 50 Hz ... 60 Hz
Discharge current to PE < 0.25 mA < 3.5 mA < 3.5 mA < 3.5 mA
Current consumption 3x 0.4 A (400 V AC) 3x 0.6 A (400 V AC) 3x 1.2 A (400 V AC) 3x 1.9 A (400 V AC)
3x 0.3 A (500 V AC) 3x 0.6 A (500 V AC) 3x 1 A (500 V AC) 3x 1.7 A (500 V AC)
2x 0.6 A (400 V AC) 2x 1.1 A (400 V AC) 2x 2.3 A (400 V AC)
2x 0.5 A (500 V AC) 2x 1.1 A (500 V AC) 2x 1.9 A (500 V AC)
Nominal power consumption 243.6 VA 451.7 VA 822.2 VA 1335.1 VA
Inrush surge current ≤ 22 A (typical) ≤ 26 A (typical) ≤ 22 A (typical) ≤ (typical)
Mains buffering typ. 20 ms (400 V AC) typ. 10 ms (400 V AC) typ. 10 ms (400 V AC) typ. 10 ms (400 V AC)
typ. 20 ms (500 V AC) typ. 20 ms (500 V AC) typ. 20 ms (500 V AC) typ. 20 ms (500 V AC)
Input fuse 3.15 A (internal (device protection), slow-blow) 3.15 A (internal (device protection), slow-blow) 3.15 A (internal (device protection), slow-blow) 6.3 A (internal (device protection))
Choice of suitable circuit breakers 6 A ... 16 A (Characteristics B, C, D, K) 6 A ... 16 A (Characteristics B, C, D, K) 6 A ... 16 A (Characteristics B, C, D, K) 10 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.55 0.58 0.63 0.77
Type of protection Transient surge protection Transient surge protection Transient surge protection Transient surge protection
Protective circuit/component Varistor Varistor Varistor Varistor
Connection data, output
Connection method Push-in connection Push-in connection Push-in connection Push-in connection
Conductor cross section solid min. 0.2 mm² 0.2 mm² 0.2 mm² 0.75 mm²
Conductor cross section solid max. 4 mm² 4 mm² 10 mm² 16 mm²
Conductor cross section flexible min. 0.2 mm² 0.2 mm² 0.2 mm² 0.75 mm²
Conductor cross section flexible max. 2.5 mm² 2.5 mm² 6 mm² 10 mm²
Conductor cross section AWG min. 24 24 24 20
Conductor cross section AWG max. 12 12 8 4
Stripping length 10 mm 10 mm 15 mm 18 mm
Ambient conditions
Degree of protection IP20 IP20 IP20 IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C -40 °C ... 85 °C -40 °C ... 85 °C -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing) ≤ 95 % (at 25 °C, non-condensing) ≤ 95 % (at 25 °C, non-condensing) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721) 3K3 (in acc. with EN 60721) 3K3 (in acc. with EN 60721) 3K3 (in acc. with EN 60721)
Degree of pollution 2 2 2 2
Installation height ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
Ambient temperature (start-up type tested) -40 °C -40 °C -40 °C
Approvals
 
  • DNV GL
  • cULus Listed
  • cULus Recognized
  • EAC
  • UL Recognized
  • cUL Recognized
  • cUL Listed
  • IECEE CB Scheme
  • UL Listed

Copyright © 2024 iComTech. All rights reserved. Shopping Cart Software powered by ecMidas.