Input Specifications |
Input voltage range |
93 – 132 VAC / 187 – 264 VAC |
nput frequency |
47 – 63 Hz |
Input current at full load (typ.) |
115 VAC/1.3 A, 230 VAC/0.75
A |
Recommended circuit breaker, characteristic C
or fuse, slow blow typ |
5.0 A |
Output Specifications |
Output voltage adj. range |
12 VDC models: 12 – 14 VDC
24 VDC models: 24 – 28 VDC
48 VDC models: 48 – 52 VDC
72 VDC models: 60 – 76 VDC |
Regulation |
|
- Input variation
- Load
variation (10–90%) |
0.2 %
1.0% |
Ripple and noise (20MHz bandwidth) |
<50 mV pk-pk |
Electronic short circuit protection |
current limitation at 110 % typ.
(constant current, automatic restart) |
Over voltage protection, trigger point at |
140 % typ. Vout nom. |
Hold-up time |
|
- 115 VAC
- 230 VAC |
min. 25 ms
min. 30 ms |
General Specifications |
Temperature ranges |
|
- Operating (ambient temp.)
- Derating
above 50°C (122°F)
- Storage
(non operating) |
–25°C to +70°C
2 %/K
–25°C to +85°C |
Humidity (non condensing) |
95 % rel. H max. |
Pollution degree |
2 |
Temperature coefficient |
0.02 %/K |
Switching frequency |
80 kHz typ. (pulse width
modulation) |
Efficiency |
85 % typ. |
Isolation |
according to IEC/EN
60950, UL 60950, UL 508 |
Reliability, calculated MTBF
(MIL-HDBK-217F, at +25°C, ground benign) |
420’000 h |
Safety standards |
IEC/EN 60950-1 (SELV,
except 72 VDC models)
UL/cUL 60950-1, UL 508, UL/cUL 1604 |
Safety approvals |
|
- CB report
- UL
approvals
- CSA
certificate (UL 60950-1,
CSA 60950-1) |
UL/cUL 60950,
File e181381
UL/cUL 508, File e210002
UL/cUL 1604, File e213613 (Class I, Div. 2, Groups A, B, C and D hazardous
locations) |
Electromagnetic compatibility (EMC), Emissions |
|
- Conducted RI suppression on input
- Radiated RI
suppression |
EN 61000-6-3 /
EN 61000-6-4
EN 55011 class B, EN 55022 class B, FCC part 15, level B
EN 55011 class A, EN 55022 class A, FCC part 15, level A |
Electromagnetic compatibility (EMC), |
E |
- Immunity
-
Electrostatic discharge (ESD)
- Radiated RF
field immunity
- Electrical
fast transient / burst immunity
- Surge
immunity
- Immunity to
conducted RF disturbances
- Power
frequency field immunity |
N 61000-6-2
IEC/EN 61000-4-2 4 kV/8 kV
IEC/EN 61000-4-3 10 V/m
IEC/EN 61000-4-4 2 kV
IEC/EN 61000-4-5 2 kV/4 kV
IEC/EN 61000-4-6 10 V
IEC/EN 61000-4-8 30 A/m |
Safety class |
degree of electrical protection 1
(IEC 536) |
Environment |
|
- Vibration
- Shock |
IEC 60068-2-6; 1 gn, 200 sweeps,
each axis
IEC 60068-2-27; 15 gn, 11 ms, each axis |
Enclosure material |
aluminium
(chassis) / zinc plated steel (cover |
Mounting (snap-on with self locking spring) |
For 35 mm DIN-rails as per EN
50022 |
Connection |
Detachable screw
terminal block (plugs included) |