Output |
DC Voltage |
24 V |
Rated Current |
5 A |
Current Range |
0 ~ 5 A |
Rated power |
120 W |
Ripple & noise (max.) Note.2 |
100mVp-p |
Voltage ADJ. range |
24 ~ 28 V |
Voltage Tolerance Note.3 |
±1.0% |
Line Regulation |
±0.5% |
Load regulation |
±1.0% |
Setup, rise Time Note.5 |
500 ms, 70 ms/230 VAC
500 ms, 70 ms/115 VAC at full load |
Hold up time (Typ.) |
36 ms/230 VAC
32 ms/115 VAC at full load |
Protection |
Overload |
105 ~ 150% rated output power |
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
Over voltage |
29 ~ 33 V |
Protection type : Shut down o/p voltage, re-power on to recover |
Environmental |
Working temp. |
-10 ~ +60 °C (Refer to output load derating curve) |
Working humidity |
20 ~ 90% RH non-condensing |
Storage TEMP., humidity |
-20 ~ +85 °C , 10 ~ 95% RH |
TEMP. Coefficient |
±0.03%/°C (0 ~ 50°C) |
Vibration |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
Safety & EMC (Note 4) |
Safety standards |
UL508, UL60950-1, TUV EN60950-1 Approved |
Withstand voltage |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
Isolation resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500 VDC |
EMI Conduction & Radiation |
Compliance to EN55011,EN55022 (CISPR22) Class B |
Hsrmonic current |
Compliance to EN61000-3-2,-3 |
EMS immunity |
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A |
DC OK Relay Contact |
Contact Close |
When the output voltage reaches the adjusted output voltage. |
Contact Open |
When the output voltage drop below 90% output voltage. |
Contact Ratings (max.) |
30V/1A resistive load |
Others |
MTBF |
136.8Khrs min.
MIL-HDBK-217F (25°C) |
Dimensions (W x H x D) |
65.5 x 125.2 x 100 mm |
Packing |
0.79 Kg; 20 pcs/16.5 Kg/1.1 CUFT |
NOTE |
- All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
- Tolerance : includes set up tolerance, line regulation and load regulation.
- The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
|